Description
- Oil Burner Primary Control
- Flame Establishing Period 15 Second
- Pilot Type Interrupted
- Voltage Rating 120 Volt AC at 60 Hertz
- Operating Temperature 32 to 140 Deg F
- Application Oil Burner
- Approval UL (Canada and US)
- Power Rating 10 Volt Amp
- Motor Load 10 Amp (Full Load)/60 Amp (Locked Rotor)
- Igniter Load 120 Volt AC 60 Hertz 500 Volt Amp
- Thermostat Anticipator Current Rating 0.2 Amp AC
- Flame Failure Response Time 1.3 Second
- Mounting 4 Inch x 4 Inch Junction Box